Specifications
Model |
DCA – 400 ESK |
Alternator |
|
50 |
60 |
Output rating(KVA) |
Continuous |
350 |
400 |
Standby |
385 |
440 |
No. of Phases |
3 – Phase, 4 – Wire |
|
50 Hz : 190~220 or 380~440
60 Hz : 190~240 or 380~480 |
Power Factor |
0.8 (Lagging) |
|
Within ± 1.0 |
Excitation |
Brushless, Rotating Exciter (With A.V.R) |
Insulation |
Class F |
Engine |
Make & Model |
Komatsu SA6D140E–3–A |
Type |
Inlined, Direct Injected, Turbocharged, Aftercooled |
Output Rating |
PS/rpm |
419/1500 |
482/1800 |
KW/min -1 |
310/1500 |
357/1800 |
No. of Cylinders-Bore X Stroke |
(mm) |
|
6–140x170 |
|
15.240 |
Fuel |
ASTM No.2 Diesel Fuel or Equivalent |
|
56 |
65.1 |
Lube Oil Sump Capacity |
(L) |
|
79 |
|
67.5 |
|
190H52 x 2 |
|
490 |
Dimensions & Weight |
|
4200 |
|
1400 |
|
2100 |
|
5470 |
Sound Level |
7m/dB (A) 1500/1800rpm |
(min -1)*3 |
|
65 |
69 |
Stock |
: |
Indent. |
Warranty |
: |
1 year / 1.000 working hours. |
Price |
: |
Contact us. |
*2 Fuel consumption is based on operation at 75% load.
*3 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.