DCA – 125 ESK

 

Specifications

Model DCA – 125 ESK
Alternator
Frequency (Hz)
50 60
Output rating(KVA) Continuous 100 125
Standby 110 138
No. of Phases 3 – Phase, 4 – Wire
Rated Voltage (V)
50 Hz : 190~220 or 380~440 60 Hz : 190~240 or 380~480
Power Factor 0.8 (Lagging)
Voltage Regulation (%)
Within ± 0.5
Excitation Brushless, Rotating Exciter (With A.V.R)
Insulation Class F
 Engine Make & Model Komatsu SAA6D102E–2–A
Type Inlined, Direct Injected, Turbocharged, Aftercooled
Output Rating  PS/rpm 97.8/1500 115.5/1800
 KW/min -1 72.5/1500 85.6/1800
No. of Cylinders-Bore X Stroke (mm)
6 – 102 x 120
Piston Displacement (L)
5.88
Fuel ASTM No.2 Diesel Fuel or Equivalent
Fuel Consumption*2 (L/h)
16.3 21.0
Lube Oil Sump Capacity  (L)
22
Coolant Capacity  (L)
26.4
Battery X Quantity
95E41R x 2
Fuel Tank Capacity  (L)
250
 Dimensions & Weight 
Length  (mm)
3000
Width  (mm)
1080
Height  (mm)
1500
Weight (kg)
2130
Sound Level
7m/dB (A) 1500/1800rpm (min -1)*3
60 63
 
Stock : Ready Stock.
Warranty : 1 year / 1.000 working hours.
Price : Contact us.
  *2 Fuel consumption is based on operation at 75% load. *3 Sound level reflects high-speed no-load operation and is calculated by averaging the measurements at four points, each 7 meters from the source.